存放Oracle Exadata设备的十六条军规:
■ Do not block ventilation openings.
■ Do not install Oracle Exadata Rack in a location that is exposed to direct sunlight or near a device that may become hot.
■ Do not install Oracle Exadata Rack in a location that is exposed to excessive d ust,corrosive gases, or air with high salt concentrations.
■ Do not install Oracle Exadata Rack in a location that is exposed to frequent
vibrations. Install Oracle Exadata Rack on a flat, level surface.
■ Use a power outlet that uses proper grounding. When using shared grounding,
the grounding resistance must not be greater than 10 ohms. Ensure that your
facility administrator or a qualified electrical engineer verifies the grounding
method for the building, and performs the grounding work.
■ Be sure that each grounding wire used for Oracle Exadata Rack is used exclusively for Oracle Exadata Rack. Also be sure to observe the precautions, warnings, and notes about handling that appear on labels on the equipment.
■ Do not place cables under the equipment or stretch the cables too tightly.
Do not disconnect power cords from the equipment while its power is on.
■ If you cannot reach the connector lock when disconnecting LAN cables, then press the connector lock with a flathead screwdriver to disconnect the cable. You could damage the system board if you force your fingers into the gap rather than using a flathead screwdriver.
■ Do not place anything on top of Oracle Exadata Rack or perform any work directly above the rack.
■ Do not let the room temperature rise sharply, especially in winter. Sudden
temperature changes can cause condensation to form inside Oracle Exadata Rack. Allow for a sufficient warm-up period prior to server operation.
■ Do not install Oracle Exadata Rack near a photocopy machine, air conditioner,
welding machine, or any other equipment that generates loud, electronic noises.
■ Avoid static electricity at the installation location. Static electricity transferred to
Oracle Exadata Rack can cause malfunctions. Static electricity is often generated on carpets.
■ Confirm the supply voltage and frequency match the electrical ratings indicated
for Oracle Exadata Rack.
■ Do not insert anything into any Oracle Exadata Rack opening, unless doing so is part of a documented procedure. Oracle Exadata Rack contains high-voltage parts. If a metal object or other electrically-conductive object enters an opening in Oracle Exadata Rack, then it could cause a short circuit. This could result in personalinjury, fire, electric shock, and equipment damage.
■ When using single phase power distribution units (PDUs), note the following:
– PDU A input 0 and PDU B input 2 must be on the same phase.
– PDU A input 1 and PDU B input 1 must be on the same phase.
– PDU A input 2 and PDU B input 0 must be on the same phase.
The inputs are labeled where they come out of the PDU. Connecting cables as
described